How Should Pit Flood Protection Devices Be Tested in Your MCP?
How Should Pit Flood Protection Devices Be Tested in Your MCP?
๐ง๐๐ผ๐ ๐ฆ๐ต๐ผ๐๐น๐ฑ ๐ฃ๐ถ๐ ๐๐น๐ผ๐ผ๐ฑ ๐ฃ๐ฟ๐ผ๐๐ฒ๐ฐ๐๐ถ๐ผ๐ป ๐๐ฒ๐๐ถ๐ฐ๐ฒ๐ ๐๐ฒ ๐ง๐ฒ๐๐๐ฒ๐ฑ ๐ถ๐ป ๐ฌ๐ผ๐๐ฟ ๐ ๐๐ฃ?๐ง
Having a well-established Maintenance Control Program is one of the keys to maintaining the highest levels of safety and protecting the value and operation of your elevator.
While the maintenance and test periods for some components and devices are clearly spelled out, others are not. Unlike earthquake detection or door lock monitoring, pit flood protection is not specifically called out in A17.1 for periodic testing or maintenance intervals.
As a result, it falls under the category ofย โ๐ด.๐ฒ.๐ญ.๐ณ.๐ฑ ๐๐ฒ๐๐ถ๐ฐ๐ฒ๐ ๐ป๐ผ๐ ๐ฐ๐ผ๐๐ฒ๐ฟ๐ฒ๐ฑ ๐ถ๐ป ๐ฆ๐ฒ๐ฐ๐๐ถ๐ผ๐ป ๐ด.๐ฒโ:
๐๐ฉ๐ฆ๐ฏ ๐ข๐ฏ๐บ ๐ฅ๐ฆ๐ท๐ช๐ค๐ฆ ๐ฐ๐ฏ ๐ธ๐ฉ๐ช๐ค๐ฉ ๐ต๐ฉ๐ฆ ๐ด๐ข๐ง๐ฆ๐ต๐บ ๐ฐ๐ง ๐ถ๐ด๐ฆ๐ณ๐ด ๐ช๐ด ๐ฅ๐ฆ๐ฑ๐ฆ๐ฏ๐ฅ๐ฆ๐ฏ๐ต ๐ช๐ด ๐ช๐ฏ๐ด๐ต๐ข๐ญ๐ญ๐ฆ๐ฅ ๐ต๐ฉ๐ข๐ต ๐ช๐ด ๐ฏ๐ฐ๐ต ๐ด๐ฑ๐ฆ๐ค๐ช๐ง๐ช๐ค๐ข๐ญ๐ญ๐บ ๐ค๐ฐ๐ท๐ฆ๐ณ๐ฆ๐ฅ ๐ช๐ฏ ๐๐ฆ๐ค๐ต๐ช๐ฐ๐ฏ 8.6, ๐ช๐ต ๐ด๐ฉ๐ข๐ญ๐ญ ๐ฃ๐ฆ ๐ช๐ฏ๐ด๐ฑ๐ฆ๐ค๐ต๐ฆ๐ฅ ๐ข๐ฏ๐ฅ ๐ต๐ฆ๐ด๐ต๐ฆ๐ฅ ๐ช๐ฏ ๐ข๐ค๐ค๐ฐ๐ณ๐ฅ๐ข๐ฏ๐ค๐ฆ ๐ธ๐ช๐ต๐ฉ ๐ต๐ฉ๐ฆ ๐ณ๐ฆ๐ฒ๐ถ๐ช๐ณ๐ฆ๐ฎ๐ฆ๐ฏ๐ต๐ด ๐ฐ๐ง ๐ต๐ฉ๐ฆ ๐ฎ๐ข๐ฏ๐ถ๐ง๐ข๐ค๐ต๐ถ๐ณ๐ฆ๐ณ’๐ด ๐ฐ๐ณ ๐ต๐ฉ๐ฆ ๐ข๐ญ๐ต๐ฆ๐ณ๐ช๐ฏ๐จ ๐ค๐ฐ๐ฎ๐ฑ๐ข๐ฏ๐บ’๐ด ๐ฑ๐ณ๐ฐ๐ค๐ฆ๐ฅ๐ถ๐ณ๐ฆ๐ด (๐ด๐ฆ๐ฆ 8.6.1.6.1 ๐ข๐ฏ๐ฅ 8.7.1.2). ๐๐ฐ๐ค๐ถ๐ฎ๐ฆ๐ฏ๐ต๐ข๐ต๐ช๐ฐ๐ฏ ๐ต๐ฉ๐ข๐ต ๐ค๐ฐ๐ฏ๐ต๐ข๐ช๐ฏ๐ด ๐ต๐ฉ๐ฆ ๐ต๐ฆ๐ด๐ต๐ช๐ฏ๐จ ๐ฑ๐ณ๐ฐ๐ค๐ฆ๐ฅ๐ถ๐ณ๐ฆ๐ด ๐ฐ๐ง ๐ต๐ฉ๐ฆ๐ด๐ฆ ๐ฅ๐ฆ๐ท๐ช๐ค๐ฆ๐ด ๐ด๐ฉ๐ข๐ญ๐ญ ๐ณ๐ฆ๐ฎ๐ข๐ช๐ฏ ๐ธ๐ช๐ต๐ฉ ๐ต๐ฉ๐ฆ ๐ฆ๐ฒ๐ถ๐ช๐ฑ๐ฎ๐ฆ๐ฏ๐ต ๐ข๐ฏ๐ฅ ๐ฃ๐ฆ ๐ข๐ท๐ข๐ช๐ญ๐ข๐ฃ๐ญ๐ฆ ๐ช๐ฏ ๐ต๐ฉ๐ฆ ๐ฐ๐ฏ-๐ด๐ช๐ต๐ฆ ๐ฅ๐ฐ๐ค๐ถ๐ฎ๐ฆ๐ฏ๐ต๐ข๐ต๐ช๐ฐ๐ฏ (๐ด๐ฆ๐ฆ 8.6.1.2.2).
Pit flood protection devices fall into a unique category, similar to governor switches, where during normal operation it is not immediately obvious if they are not working. A non-functioning device often becomes apparent only when it is needed, which is typically too late.
๐ช๐ฒ ๐ฟ๐ฒ๐ฐ๐ผ๐บ๐บ๐ฒ๐ป๐ฑ ๐๐ต๐ฒ ๐ณ๐ผ๐น๐น๐ผ๐๐ถ๐ป๐ด ๐๐ต๐ฒ๐ป ๐ฐ๐ผ๐บ๐ฝ๐ถ๐น๐ถ๐ป๐ด ๐๐ผ๐๐ฟ ๐ ๐๐ฃ:
1.ย ย ย ย ย ย ย ย ย Add pit flood protection devices into your Category 1 testing, similar to governor switches, DLM, and earthquake detection.
2.ย ย ย ย ย ย ย ย ย Test functionality any time a component the pit flood protection device is connected to is changed, especially if the COP button or hall button it is connected to is replaced.
3.ย ย ย ย ย ย ย ย ย Test after any major overhaul.
Pit flood protection has the ability to prevent tens of thousands of dollars in damage to an elevator during flooding caused by a storm or burst pipe. Additionally, it provides an extra layer of safety to passengers by keeping them from descending into a flooded pit. The time to determine whether or not the device is still connected and functioning is before it is needed, not after.